DKG-307 User Manual V-01.03
(14.02.2006)
- 17 -
Pgm Definition Unit Std Val Description
8 Low Freq. Alarm Hz 30
If the genset frequency goes under this limit, a
SPEED alarm will be generated and the engine
will stop. This alarm will be monitored after delay
defined in P_023 when the engine runs.
9 Low Freq. Warning Hz 40
If the genset frequency goes under this limit, a
SPEED warning will be generated. This warning
will be monitored after delay defined in P_023
when the engine runs.
10 High Freq. Warning Hz 54
If the genset frequency goes over this limit, a
SPEED warning will be generated. This warning
will be monitored after delay defined in P_023
when the engine runs.
11 High Freq. Alarm Hz 57
If the genset frequency goes over this limit, a
SPEED alarm will be generated and the engine
will stop. This alarm will be monitored after delay
defined in P_023 when the engine runs.
12
Low Battery Voltage
Warning
V 9.0
If the battery voltage falls below this limit, this
will generate a BATTERY warning.
13
High Battery Voltage
Warning
V 31.0
If the battery voltage goes over this limit, this
will generate a BATTERY warning.
14
High Battery Voltage
Alarm
V 33.0
If the battery voltage goes over this limit, this
will generate a BATTERY alarm and the
engine will stop.
15
Low Oil Pressure
Warning
Bar 1.5
If the oil pressure measured from the analog
input falls below this limit, this will generate an
OIL PRESSURE warning. This input will be
monitored after delay defined in P_023 when the
engine runs.
16 Low Oil Pressure Alarm Bar 1.0
If the oil pressure measured from the analog
input falls below this limit, this will generate an
OIL PRESSURE alarm. This input will be
monitored after delay defined in P_023 when the
engine runs.
17
High Temperature
Warning
ºC 90
If the coolant temperature measured from the
analog input goes over this limit, this will
generate a HIGH TEMP. warning.
18 High Temperature Alarm
ºC 98
If the coolant temperature measured from the
analog input goes over this limit, this will
generate a HIGH TEMP. alarm and the engine
will stop.
19 Oil pressure sender type - 1
This parameter selects the oil pressure sender
type.
0: Non standard sender. The sender
characteristics are defined in table using
parameters P_131 to P_142.
1: VDO 0-7 bars (10-180 ohms)
2: VDO 0-10 bars (280-20 ohms)
3: DATCON 0-7 bars (240-33 ohms)
4: DATCON 0-10 bars (240-33 ohms)
5: DATCON 0-7 bars (0-90 ohms)
6: DATCON 0-10 bars (0-90 ohms)
7: DATCON 0-7 bars (75-10 ohms)
20 Temperature sender type - 1 This parameter selects the temperature sender
type:
0: The sender characteristics are defined in
table using parameters P_143 to P_154.
1: VDO
2: DATCON DAH type
3: DATCON DAL type
Komentarze do niniejszej Instrukcji