DKG-307 User Manual V-01.03
(14.02.2006)
- 21 -
Parameters from P_083 to P_130 program the functions of the digital inputs. The programmable
properties of digital inputs are:
-action to be taken upon arrival of the fault signal (alarm, warning,etc...),
-when the fault monitoring will be enabled,
-latching of the fault signal,
-contact type (NO/NC)
-switching (bat+, bat-)
-response delay
LOW OIL PRESSURE SWITCH INPUT
Pgm Description Std
83 Operation 0
0: Alarm (the engine stops and horn relay operates))
2: Warning (the horn relay operates)
3: No operation
84 Fault monitoring 1
0: Always
1: After holdoff timer
2: When mains present
85 Latching 1
0: Non latching
1: Latching
86 Contact type 0
0: Normally open
1: Normally closed
87 Switching 0
0: Battery negative
1: Battery positive
88 Response delay 0
0: No delay
1: Delayed (4sec)
HIGH TEMPERATURE SWITCH INPUT
Pgm Description Std
89 Operation 0
0: Alarm (the engine stops and horn relay operates))
2 Warning (the horn relay operates)
3 No operation
90 Fault monitoring 0
0: Always
1: After holdoff timer
2: When mains present
91 Latching 1
0: Non latching
1: Latching
92 Contact type 0
0: Normally open
1: Normally closed
93 Switching 0
0: Battery negative
1: Battery positive
94 Response delay 0
0: No delay
1: Delayed (4sec)
COOLANT LEVEL SWITCH INPUT
Pgm Description Std
95 Operation 0
0: Alarm (the engine stops and horn relay operates))
2: Warning (the horn relay operates)
3: No operation
96 Fault monitoring 0
0: Always
1: After holdoff timer
2: When mains present
97 Latching 0
0: Non latching
1: Latching
98 Contact type 0
0: Normally open
1: Normally closed
99 Switching 0
0: Battery negative
1: Battery positive
100 Response delay 1
0: No delay
1: Delayed (4sec)